Type Tests on Suspension Clamp for HTLS Conductor
The tests are listed according to the Guidelines for Rationalized Use of High Performance Conductors
Central Electricity Authority (CEA)
Magnetic Power Loss Test
This type test measures the magnetic losses of suspension clamps. The test shall be carried out as agreed between purchaser and supplier.
Here, we pass a power frequency current through a suitable length of conductor. Then we measure the power loss. Now, we fit a certain number of suspension clamps on the conductor. Again, we measure the wattage with the fittings assembled on the conductor. In case of AG suspension clamps, we assemble the armour rods.

We keep the test circuit geometry exactly the same for both measurements. In each case, we allow the conductor to reach its steady temperature.

To measure the power losses of the fittings, the standards recommends to use a minimum five suspension clamps. We mount the clamps on the conductor with a minimum spacing between them not less than 50 cm. The fittings under test shall be complete with all components assembled as defined in the supplier’s drawing of the fitting.
We apply an AC voltage at a frequency of 50 Hz. We keep the magnitude of the current according to table given bellow.
| Conductive cross-section (mm²) | Aluminium and aluminium alloy (A) |
|---|---|
| 25 | 115 |
| 50 | 175 |
| 75 | 230 |
| 100 | 275 |
| 150 | 355 |
| 200 | 435 |
| 250 | 500 |
| 300 | 565 |
| 400 | 680 |
| 500 | 785 |
| 600 | 875 |
| 700 | 955 |
| 800 | 1 025 |
| 900 | 1 100 |
| 1 000 | 1 170 |
Acceptance criteria
We accept the test if the magnetic losses of the clamps are less than or equal to the power losses per unit length of the conductor. The condition corresponds to the relation:\[ \frac{P_D-P_C}{N}\leq \frac{P_C}{L} \]Where, \(P_C\) = the power losses of the reference length of the conductor without fittings, in watts;
\(P_D\) = the power losses of the reference length of the conductor with fittings, in watts;
\(L\) = the reference length of the conductor in metres;
\(N\) = the number of fittings mounted.
Clamp Slip Strength
As per IS 2486 (Part 2), the slip strength test is conducted on an Armour Grip (AG) type suspension clamp by applying a horizontal tensile load to the conductor after the conductor has been properly fitted in the AG suspension clamp.

During the test, the applied horizontal load shall be not less than 12.5% of the Ultimate Tensile Strength (UTS) of the conductor. The UTS of the conductor can be obtained from the approved GTP (Guaranteed Technical Particulars) or from the relevant conductor specification. The maximum horizontal load applied to the conductor during the slip strength test shall be less than 20% of the UTS of the conductor.

The CEA guideline provides an example for a 400 kV transmission system. In this example, the horizontal tensile load applied during the slip strength test is specified within the range of 20 kN to 29 kN. In other words, for the particular conductor and clamp arrangement covered by that example, the applied horizontal tensile load should be not less than 20 kN and not more than 29 kN, subject to the applicable test requirements.
Ozone Test on Elastomer
Vertical Damage Load and Failure Load Test — IEC: 61284
We carry out the test according to the same or equivalent arrangement shown on the image below.

We mount the clamp in a tension testing machine. Here we have shown only the arrangement of the clamp portion.

For Armour Grip Suspension Clamp or AG Suspension Clamp we shall apply armour rods to the conductor. Since, armour rods are used in actual service of the clamp.

First step : Then we increase the load gradually to the specified minimum damage load (SMDL). Then we keep it constant for 1 minute or 60 s. After that, we unload the clamp. Lastly we perform measurements of the permanent deformations. Actually we marked points at different locations on the tensed part of the clamp. Then we measure the point to point distance to ensure degree of deformation during the test.
Second step : Now instead of the conductor, we insert a rigid bar of suitable size in the clamp. The we install it on in the tension testing machine.

Now, we load the clamp gradually increase the load to the specified minimum failure load (SMFL).

Then we keep the load constant for 60 seconds again. Thereafter, we gradually increase the load until failure of the fitting.

NOTE — For very high mechanical failure loads, we can stop the test at 1.2 times the specified minimum failure load. This is in the view of the safety of equipment and operators.
Type Tests on Dead end Tension Assembly
Electrical Resistance Test for Dead End Assembly — As per IS:2486-(Part-I)
Tension joints and anchor clamps are important parts of overhead transmission lines. They must provide both mechanical strength and good electrical contact. A poor electrical connection creates resistance. This causes power loss and heating. Over time, excessive heating can damage the fitting and affect the reliability of the line. The resistance test checks the electrical performance of the fitting.
The main purpose is simple. The fitting must not add excessive resistance to the current path. This test applies to:
- Tension joints
- Anchor clamps
- Jumper connections
- Other current-carrying parts of the fitting
The test is especially important when the conductor is not electrically continuous through the clamp.
Procedure
First, assemble the fitting as recommended by the manufacturer. After assembly, measure the resistance across the fitting. Take voltage measurements at two points on the conductor. Place one point on each side of the fitting. Keep each measuring point at least 25 mm clear of the fitting.

Acceptance Criterion
The resistance of the fitting must not exceed 75% of the resistance of an equivalent length of conductor. We can express this as: R(fitting) ≤ 0.75 × R(equivalent conductor length).
For example, suppose the resistance of the equivalent conductor length is 100 µΩ.
Then, Maximum fitting resistance = 0.75 × 100 = 75 µΩ.
Therefore, the measured resistance of the fitting must not exceed 75 µΩ. This limit is important. A high-resistance joint produces additional power loss.
Perform the resistance test using direct current (DC). The current connections must be sufficiently far from the fitting. Keep each current connection at least 50 times the conductor diameter away from the fitting. For example, consider a conductor with a diameter of 30 mm. The minimum distance is: 50 × 30 = 1,500 mm. Therefore, the current connection should be at least 1.5 metres away from the fitting.
The current connection must make effective electrical contact with all strands of the conductor. This is very important for stranded conductors. Poor contact with some strands can cause uneven current distribution. This can produce an incorrect resistance reading. Therefore, always ensure good contact with all conductor strands before taking the measurement.
Measurement With Reverse Polarity
Take two resistance measurements. First, apply the DC current in one direction. Record the resistance. Then reverse the polarity. Measure the resistance again. Take the average of the two readings. For example,
First reading = 60 µΩ
Reverse-polarity reading = 62 µΩ
Therefore,
Final resistance = (60 + 62) ÷ 2 = 61 µΩ
So, the final measured resistance is 61 µΩ.
Very low resistance measurements can be affected by small unwanted voltages. One common source is thermoelectric EMF. It can develop at connections between different metals. These unwanted voltages may introduce errors into micro-ohm measurements. Reversing the DC polarity changes the effect of these unwanted voltages. Taking the average of both readings helps reduce the error.
b) Heating cycle test for dead end Assembly — As per Appendix-I
c) Slip strength test for dead end assembly — As per Appendix-I
d) Ageing test on filler (if applicable) — As per Appendix-I