Some the important parameters are listed here for the reference only. The actual technical parameters of a potential transformer may be somewhat different depending on the actual requirements.
- Potential Transformers are of
1. Electromagnetic Type,
2. Outdoor Type,
3. Single Phase,
4. Oil filled self cooling type,
5. with Porcelain Housing. - The Standards to be followed for a Potential or Voltage Transformers
1. IS 3156 (Part 1 to 4)
2. IS 4146 – Application guide for Voltage Transformers - Temperature Rise Limits
1. Maximum Winding Temperature Rise Limit is 50oC above ambient
2. Maximum Oil Temperature Rise Limit is 40oC above ambient
3. Maximum Ambient Temperature Limit is 50oC . - The P.T. shall have
1. Terminal box for secondary connection,
2. Lifting lugs,
3. Grounding terminals,
4. Oil sight glass,
5. Pressure relief device,
6. Filling and draining plugs. - The core of the potential transformer should be made of
1. CRGO silicon Steel or
2. Nanocrystalline materials. - The PT winding shall be made of copper.
- The secondary terminals shall be brought out through fuse of suitable rating.
- PT junction box to C&R panel must be connected with 4 sqmm color coded (Red, Yellow, Blue, Black) copper cable.
- Two grounding terminals on diagonally opposite sides shall be provided.
- The lower end of the high-voltage winding is brought out through a bushing to insulate it from the case or frame. That terminal of the high-voltage winding shall be earthed separately.
- The PT secondary terminal box shall be made of a 3 mm thick sheet of steel. However, some utilities accept a 2 mm thick sheet, but for outdoor applications, 3 mm is preferable according to many experienced engineers.
- The degree of protection tghe secondary terminal box shall not be less than IP-55.
- The door shall have a braided copper wire connecting it to the main body for earthing.
- The tank and top chamber shall be hot-dip galvanized or painted. An aluminum top chamber is also acceptable.
- Steel surfaces exposed to insulating oil shall be coated with a heat-resistant, oil-repellent insulating varnish.
- Voltage Factor
1.5 times for 30 sec, 1.2 continuous (for 400 KV, 220 KV, and 132 KV)
1.9 times for 8 Hrs, 1.2 continuous (for 33 KV) - PTs shall be of accuracy class 0.2 for metering and 3P for protection.