Type Tests of SF6 Circuit Breakers as per IS-13118:
- Dielectric Tests – Power frequency voltage withstand test
- Lightning impulse test
- Switching impulse test for greater than 300kV rated CB
- Radio Interference Voltage (RIV) test
- Temperature Rise Test
- Measurement of resistance of main circuit of the CB
- Short-time withstand current and peak withstand current test
- Mechanical and environmental tests
- Tightness test
- Electromagnetic capability test
- High voltage test on auxiliary and control circuit.
Routine Tests on SF6 Circuit Breaker as per IS-12729.
- Dielectric test on main circuit.
- High voltage test on auxiliary and control circuit.
- Measurement of resistance of main circuit.
- Tightness tests.
- Design and visual test.
Acceptance Tests on SF6 Circuit Breaker
- Visual check.
- Verification of order related features.
- Checking the identification marks, stickers, name plate and general aesthetics.
- Mechanical operation test.
- 5 closing operation at 100% rated control voltage,
- 5 opening operation at 100% rated control voltage,
- 5 closing operation at 85% rated control voltage,
- 5 opening operation at 70% rated control voltage,
- 5 closing operation at 110% rated control voltage,
- 5 opening operation at 110% rated control voltage.
- Measurement of operating times at 100% of rated control voltage for closing, opening and close-open operations.
- Gas leakage test
- Electrical Sequence Check
- Checking the control circuit as per approved drawings
- Checking the function of anti-pumping
- Checking the function of auxiliary AC circuits,
- Measurement of spring charging time and motor current,
- 1KV for 1sec test or 2KV for 60sec test on control and auxiliary circuits of the CB,
- Checking and verification of operation of SF6 density monitor switch,
- One minute power frequency withstand test on the main circuit of CB,
- Closing and tripping coil resistance measurement,
- Contact measurement or milli-volt drop test on the main contacts of the CB during close condition.